Passive Fire Protection \\ {Intumescent Coatings}

Intumescent coatings
for structural steel

A thin-film or epoxy coating that expands into an insulating char under heat and holds the steel section below its critical temperature for the rated period. Certified across the cellulosic, hydrocarbon and RWS fire curves. [Supply, or SITC] across India.

The three curves

A coating certified on one curve is not evidence on another

1400105070035000306090120minutes°Csteel critical temperature, typically 550°C
  • Cellulosic · peak ~1050°C at 120 min
  • Hydrocarbon · plateau ~1100°C from 30 min
  • RWS · peak ~1350°C at 60 min

Cellulosic, defined in ISO 834 and BS 476 Part 20. A fire fed by timber, paper and finishes, reaching around 1,000°C in the first hour. This curve governs almost all building steelwork: high-rise frames, airports, malls, warehousing and data centre structures.

Fire tests are run against a defined temperature-time curve, and the curve is chosen to represent what actually burns in the building. Ratings under these curves are [R 120] on cellulosic and [R 240] on hydrocarbon and RWS, against the certified thickness tables for the specific product. The certificate covers the tested configuration, section factor and exposure, not the member on the drawing.

What the rating establishes

A coating delivers R, and only R

An intumescent coating delivers R, loadbearing capacity. It keeps the section below its critical temperature so the member carries its load for the rated period. It does not deliver E, integrity, or I, insulation. A coated column is not a fire barrier, and an enquiry asking for EI 120 on bare steelwork is asking a coating to do something no coating does.

That distinction decides the product before any thickness is discussed. If the requirement is to keep a structure standing, it is a coating. If the requirement is to stop fire crossing a plane, it is firestopping or a rated wall.

What we need to price a coating

Four inputs, and a specification that omits them will come back as three quotes that do not compare.

The critical temperature of each member, which is its true limiting temperature under the actual load, not the 550°C most tables assume by default. The section factor, Hp/A, and the exposure it is calculated for, since a three-sided beam and a four-sided column of the same section resolve to different thicknesses under the same rating. The environment, internal, external or corrosive, which decides the primer and topcoat system and the corrosivity category the build-up has to meet. And whether application is off site or on site, which changes the programme more than it changes the product.

From those we return a dry film thickness per member, the certified table it is read from, and the evidence behind it. Thickness may be interpolated inside a certified range. It is never extrapolated beyond one.

Applications & Performance
Fire rating[R 120]cellulosic curve, to [R 240] on hydrocarbon and RWS
Curves certifiedThreecellulosic, hydrocarbon, RWS
ApplicationsSteel frameshigh-rise, data centres, industrial plant, road and metro tunnels
Scope[Supply, or SITC]across India
Terminology

Intumescent coating, intumescent paint, fireproof paint

Intumescent coating, intumescent paint and fire protection coating describe the same product. On Indian tenders you will also see fireproof paint, fire retardant paint and steel fireproofing, and the BOQ line is often written as supply and application of intumescent fire protection coating to structural steel.

Two of those names describe something different and get confused with it. A fire retardant paint in the strict sense improves a surface’s reaction to fire, its spread of flame, and does not give a structural member a fire resistance rating. Sprayed cementitious or vermiculite protection also delivers R, but as a thick applied layer rather than a char-forming film, with a different finish, thickness and cost profile.

Getting the vocabulary right matters commercially because the evidence is product-specific. A thickness read from one manufacturer’s table is not valid for another’s, whatever the two tins say on the label. The same logic runs through the rest of the passive layer, including cavity barriers, where the certificate covers a tested configuration rather than the nominal opening on the drawing.

Standards and evidence

Structural steel coatings are tested and classified under [EN 13381-8], [BS 476 Part 21] and [ISO 834], with [UL 263] for cellulosic exposure and [UL 1709] for hydrocarbon. Tunnel work is assessed against the RWS curve.

Those certificates are held by the manufacturer and cover the tested system, which is the primer, the intumescent and the topcoat as a build-up. Agnimatic supplies [product families] against that evidence and provides the certificate, the thickness table and the classification report on request. Agnimatic’s own scope on this line is [Supply, or SITC].

Common questions

What does an intumescent coating do?

Under heat it expands to many times its applied thickness and forms an insulating carbonaceous char. The char slows heat transfer into the steel, keeping the section below its critical temperature so the member holds its load for the rated period. It protects the structure. It does not seal an opening.

How thick does intumescent coating need to be?

There is no single figure. Thickness is read from the certified table for that specific product against the member’s section factor, its exposure, its critical temperature and the required rating. The same rating on the same frame produces different thicknesses on different members.

Is intumescent paint the same as fire retardant paint?

No. An intumescent coating gives a structural member a fire resistance rating for a stated period. A fire retardant paint improves how a surface reacts to fire and does not carry a structural rating. Specifications that use the terms interchangeably usually mean the first.

Send the member schedule with section sizes, exposure and the rating required, and we will return thicknesses against the certified tables and the evidence that covers them.

Enquire now

TESTED TO THE CURVE.RATED FOR THE WORST.